The information on the website is for informational purposes only. Calculation results should be interpreted by the designer. The information contained in the service does not constitute technical advice. The user is responsible for all decisions, selections or solutions based on calculation results.
© 2025 KalkulatorPro
This website uses cookies to provide services at the highest level. By continuing to use the site, you agree to their use. Cookies are used for:
For more information about cookies and how to manage them, please visit our Privacy Policy
enter the valve authority (default set to 0.5); circuit resistance where the valve will be installed (without this valve's resistance) and enter the flow in m3/h or dm3/s for the program to calculate the required Kv value of the valve and pressure drop across this valve in bars.
Recommended authority is 0.3 - 0.7. The maximum authority value that can be entered for calculations is 0.99
In the second calculation type, select a valve with the appropriate kvs and flow in m3/h or dm3/s for the program to calculate the pressure drop on the actual valve in bars and kilopascals
Additionally, the application will calculate the real valve authority by comparing the actual valve pressure drop to the installation resistances
When entering flow in m3/h, the program will convert it to dm3/s and vice versa.