calculator logoKalkulatorPro

Ventilation Duct Sizing - Installation Designer's Guide

8 marca 2026 | Ventilation


Proper ventilation duct sizing is one of the key stages in designing a mechanical ventilation system. A duct that is too small means excessive noise and high flow resistance, while one that is too large unnecessarily increases costs and takes up valuable space. In this guide, we present a complete methodology for sizing round (spiro) and rectangular ducts, including formulas, tables and calculation examples.

If you need to quickly size a duct, use our ventilation duct sizing calculator, which automatically selects the diameter or duct dimensions based on the required airflow.

Spiro ventilation ducts

Fundamentals of Ventilation Duct Sizing

Ventilation duct sizing involves determining a cross-section that ensures the transport of the required amount of air at an acceptable flow velocity and pressure drop. In design practice, two methods are used:

  • Constant velocity method - the duct is sized so that the air velocity does not exceed a specified maximum value
  • Equal friction method - the duct is sized so that the unit pressure losses (Pa/m) are similar across all sections of the system

Regardless of the method chosen, the starting point is knowing the required airflow in a given section of the system.

Recommended Air Velocities in Ducts

The air velocity in a ventilation duct has a direct impact on noise levels and pressure drops. Recommended values depend on the required noise level in the room and on the location of the duct in the system. The table below shows recommended and maximum velocities depending on acoustic requirements:

Required noise levelRecommended velocitiesMaximum velocities
duct at fan [m/s]main or distribution duct [m/s]branch near diffuser [m/s]duct at fan [m/s]main or distribution duct [m/s]branch near diffuser [m/s]
Low84 - 53 - 41065
Normal94 - 54 - 51266
Loud95 - 75 - 61287
Industrial buildings106 - 95 - 914119
Velocities at System Components
System componentRecommended velocity [m/s]Maximum velocity [m/s]
Exhaust outlets4.05.5
Air intakes2.54.5 - 6.0
Air filters1.52.0
Heating coils2.53.0

In residential buildings, the velocity in branches near diffusers should be approximately 2 - 2.5 m/s, and in main ducts it should not exceed 5 m/s.

Exceeding recommended velocities results in increased noise generated by the flowing air and significantly higher flow resistance, which requires a more powerful fan.

Round Ducts (Spiro) - Sizing and Calculations

Round spiro ducts are the most commonly used solution in mechanical ventilation. They are characterised by the lowest flow resistance relative to the cross-section, simple installation and wide availability.

Standard Spiro Duct Diameters

Spiro ducts are manufactured in standardised diameters (mm): 80, 100, 125, 160, 200, 250, 315, 355, 400, 450, 500, 630, 710, 800, 1000, 1250.

Flow Velocity in a Round Duct

The air velocity in a round duct is calculated using the formula:

v=4V˙3600πd2 [m/s]v = \frac{4 \cdot \dot{V}}{3600 \cdot \pi \cdot d^2} \ [\mathrm{m/s}]

where:

  • V˙\dot{V} - airflow [m³/h]
  • dd - internal duct diameter [m]
Pressure Drop in a Round Duct

The unit pressure drop (per running metre of duct) is calculated using the Darcy-Weisbach equation:

Δp=λ1dρv22 [Pa/m]\Delta p = \lambda \cdot \frac{1}{d} \cdot \frac{\rho \cdot v^2}{2} \ [\mathrm{Pa/m}]

where:

  • λ\lambda - friction factor (determined iteratively from the Colebrook-White equation)
  • dd - internal duct diameter [m]
  • ρ\rho - air density (assumed 1.2 kg/m³ at 20°C)
  • vv - flow velocity [m/s]

The friction factor λ\lambda depends on the Reynolds number and duct roughness. The Reynolds number is calculated as:

Re=vdνRe = \frac{v \cdot d}{\nu}

where ν\nu = 15.1 × 10⁻⁶ m²/s is the kinematic viscosity of air at 20°C.

Duct Roughness - Impact on Pressure Drop

The type of duct material has a significant impact on flow resistance. The parameter describing this impact is the absolute roughness (k):

Duct typeRoughness k [mm]

Galvanised steel rectangular

0.15

Galvanised steel spiro (round)

0.10

Plastic (PVC, PP)

0.03

Flex duct stretched

0.75

Flex duct compressed / bent

2.00

As can be seen, flexible ducts have many times higher roughness than rigid ducts. For this reason, flexible ducts should only be used on short connection sections (to diffusers, plenum boxes, etc.) and always in a stretched state.

Rectangular ventilation ducts

Rectangular Ducts - Sizing and Calculations

Rectangular ducts are used where the height of the installation space is limited (e.g. suspended ceilings, installation shafts). They have worse aerodynamic properties than round ducts but allow better adaptation to available space.

Hydraulic (Equivalent) Diameter

The key concept in rectangular duct calculations is the hydraulic diameter, which allows the same formulas to be used as for round ducts:

dh=2aba+b [m]d_h = \frac{2 \cdot a \cdot b}{a + b} \ [\mathrm{m}]

where:

  • aa - dimension of side A of the duct [m]
  • bb - dimension of side B of the duct [m]

The hydraulic diameter is always smaller than the shorter side of the duct. This means that for the same cross-sectional area, a rectangular duct has higher pressure drops than a round one.

Flow Velocity in a Rectangular Duct

v=V˙3600ab [m/s]v = \frac{\dot{V}}{3600 \cdot a \cdot b} \ [\mathrm{m/s}]

where aa and bb are the side dimensions in metres.

Pressure Drop in a Rectangular Duct

The Darcy-Weisbach formula for a rectangular duct:

Δp=λ1dhρv22 [Pa/m]\Delta p = \lambda \cdot \frac{1}{d_h} \cdot \frac{\rho \cdot v^2}{2} \ [\mathrm{Pa/m}]

In this formula, the hydraulic diameter dhd_h is used instead of the duct diameter. The friction factor λ\lambda is determined analogously to round ducts, but using the hydraulic diameter in the Reynolds number.

Recommended Aspect Ratio

When sizing rectangular ducts, the aspect ratio a/b is important. It is recommended that this ratio does not exceed 4:1. Ducts with a very flat profile (e.g. 8:1) have significantly higher resistance and are more difficult to install.

Aspect ratio a/bRating

1:1 (square)

Aerodynamically optimal

up to 2:1

Recommended

2:1 to 4:1

Acceptable

above 4:1

Not recommended - high resistance

Round vs. Rectangular Ducts - Comparison

Comparison of round spiro and rectangular duct

The choice between round and rectangular duct is a common design dilemma. Below is a comparison of the key features of both solutions:

FeatureRound (spiro)Rectangular

Flow resistance

LowerHigher (by 20-40%)

Air tightness

Very goodRequires sealing

Required installation space

Greater heightSmaller height

Material cost

LowerHigher

Installation speed

FasterSlower

Acoustic insulation

BetterWorse (wall resonance)

Dimensional flexibility

Stepped (standard range)Any (in 50 mm increments)

In most cases, round spiro ducts are preferred due to lower resistance, better air tightness and lower cost. Rectangular ducts are chosen primarily for spatial reasons.

Spiro duct installation in a commercial building

Calculation Example - Round Duct

Let us assume we need to size a spiro duct for a supply section with an airflow of 500 m³/h in an office building (max. velocity 4.5 m/s).

Step 1: Determining the minimum cross-section

Minimum duct cross-sectional area:

Amin=V˙3600vmax=50036004,5=0,0309 m2A_{min} = \frac{\dot{V}}{3600 \cdot v_{max}} = \frac{500}{3600 \cdot 4{,}5} = 0{,}0309 \ \mathrm{m}^2

Step 2: Determining the minimum diameter

dmin=4Aminπ=40,03093,14=0,198 m=198 mmd_{min} = \sqrt{\frac{4 \cdot A_{min}}{\pi}} = \sqrt{\frac{4 \cdot 0{,}0309}{3{,}14}} = 0{,}198 \ \mathrm{m} = 198 \ \mathrm{mm}

Step 3: Selection from the standard range

The nearest larger standard diameter is 200 mm.

Step 4: Velocity verification

v=45003600π0,22=4,42 m/sv = \frac{4 \cdot 500}{3600 \cdot \pi \cdot 0{,}2^2} = 4{,}42 \ \mathrm{m/s}

The velocity of 4.42 m/s is within the acceptable range for offices.

Step 5: Unit pressure drop

For a spiro duct (k = 0.1 mm) with a diameter of 200 mm and an airflow of 500 m³/h, the unit pressure drop is approximately 1.7 Pa/m. This value is typical and acceptable - the recommended range is 0.5-2.5 Pa/m.

All the above calculations can be performed automatically using our ventilation duct sizing calculator.

Calculation Example - Rectangular Duct

For the same airflow of 500 m³/h, we need to size a rectangular duct with a limited installation height of 250 mm.

Step 1: Fixing one dimension

We assume side B = 200 mm (leaving room for insulation).

Step 2: Determining the other side

amin=V˙3600vmaxb=50036004,50,2=0,154 m=154 mma_{min} = \frac{\dot{V}}{3600 \cdot v_{max} \cdot b} = \frac{500}{3600 \cdot 4{,}5 \cdot 0{,}2} = 0{,}154 \ \mathrm{m} = 154 \ \mathrm{mm}

We assume side A = 200 mm (rounding up to the nearest standard dimension in 50 mm increments).

Step 3: Verification

Duct 200 × 200 mm:

  • Velocity: v=50036000,20,2=3,47 m/sv = \frac{500}{3600 \cdot 0{,}2 \cdot 0{,}2} = 3{,}47 \ \mathrm{m/s}
  • Hydraulic diameter: dh=2200200200+200=200 mmd_h = \frac{2 \cdot 200 \cdot 200}{200 + 200} = 200 \ \mathrm{mm}
  • Aspect ratio: 1:1 (optimal)

The velocity of 3.47 m/s is comfortable and ensures a low noise level.

Typical Room Airflow Rates

When designing ventilation, the starting point is the required airflow. Below are the most commonly used values in accordance with the PN-83/B-03430 standard and Technical Requirements:

RoomRequired exhaust airflow

Kitchen with window (gas cooker)

70 m³/h

Kitchen with window (electric cooker)

50 m³/h

Kitchen without window

70 m³/h

Bathroom

50 m³/h

WC

30 m³/h

Auxiliary room without window

15 m³/h

Living room (per person)

30 m³/h

Local Resistances - Fittings and System Components

In addition to linear losses in straight duct sections, local resistances generated by fittings occur in a ventilation system. These resistances are calculated using the formula:

Δpm=ζρv22 [Pa]\Delta p_m = \zeta \cdot \frac{\rho \cdot v^2}{2} \ [\mathrm{Pa}]

where ζ\zeta is the local resistance coefficient, dependent on the type of fitting.

Typical values of the ζ\zeta coefficient:

ComponentCoefficient ζ\zeta [-]

90° elbow (round, smooth)

0.15 - 0.30

90° elbow (rectangular, without turning vanes)

1.10 - 1.30

90° elbow (rectangular, with turning vanes)

0.15 - 0.25

Tee - straight flow

0.10 - 0.50

Tee - branch

0.50 - 1.50

Damper (open)

0.10 - 0.20

Wall intake / exhaust terminal

2.0 - 3.5

Supply diffuser

per manufacturer's data

It is worth noting rectangular elbows without turning vanes - they generate several times higher resistance than round elbows. Installing turning vanes in rectangular elbows significantly reduces resistance.

Most Common Mistakes in Duct Sizing

1. Too narrow ducts in pursuit of savings - the designer selects a smaller cross-section to reduce material cost. As a result, pressure drops increase, requiring a more powerful (and more expensive) fan and generating higher noise.

2. Underestimating local resistances - in practice, resistances at fittings can account for 50-70% of the total system resistance. Omitting them from calculations leads to undersizing of the fan.

3. Using long sections of flexible ducts - flex ducts have many times higher roughness than rigid ducts. Even 2-3 metres of unstretched flex can generate resistance comparable to several tens of metres of spiro duct.

4. Ignoring the aspect ratio of rectangular ducts - ducts with proportions above 4:1 have significantly higher resistance and are prone to deformation. It is better to use two smaller ducts instead of one with extreme proportions.

5. No margin for regulation - sizing at the limit of maximum velocity leaves no margin for system regulation and possible future airflow adjustments.

Summary

Proper ventilation duct sizing requires consideration of the required airflow, permissible velocity, pressure drops and spatial conditions. Round spiro ducts should be the first choice due to better aerodynamic properties and lower cost. Rectangular ducts are used where limited installation space requires it.

To speed up your design work, use our ventilation duct sizing calculator, which automatically selects the round duct diameter or calculates the flow parameters for a rectangular duct with specified dimensions.

Back to articles list