calculator logoKalkulatorPro

Voltage drop in electrical installations — how to calculate it and when it becomes a problem?

26 marca 2026 | Electrical


Every electrical cable resists the flow of current — the longer the cable and the higher the current, the more voltage is "lost" along the way. In domestic installations with short circuits, this issue is often overlooked. But a longer cable run, outdoor lighting, or a photovoltaic installation is all it takes for voltage drop to become the deciding factor in cable cross-section selection.

If you want to quickly check the voltage drop for a specific circuit, use our voltage drop calculator. Below we explain the theory, standards, and practical cases where voltage drop is of critical importance.

Voltage drop in electrical installation

What is voltage drop?

Voltage drop is the difference in potential between the beginning and end of a cable, caused by its resistance (and reactance for larger cross-sections). If we have 230 V at the distribution board terminals and measure 218 V at a socket in a workshop 50 m away — the voltage drop is 12 V, or 5.2%.

Consequences of excessive voltage drop:

  • flickering or dimming of lighting — particularly noticeable with LEDs,
  • reduced motor power — torque drops with the square of voltage,
  • equipment starting problems — motors, compressors, and heat pumps may fail to start,
  • cable overheating — at reduced voltage, equipment draws higher current to maintain power,
  • damage to sensitive electronics — switch-mode power supplies may operate erratically.

Permissible voltage drops according to standards

Standard PN-HD 60364-5-52 (and its Polish equivalent) defines maximum voltage drops in consumer installations, measured from the point of supply to the load:

Supply sourceLightingOther loads

Type A — public network supply

3%5%

Type B — private source supply (generator, UPS)

6%8%

These values apply to the entire route from the point of supply to the load. In practice, this means that the voltage drop on the main supply line (riser cable) and on the final circuit adds up — as we discuss in the section on cascading drops.

The standard allows increasing the above limits by 0.005% for each metre beyond 100 m of route length, but by no more than an additional 0.5%.

Voltage drop formulas

Simplified formula (resistance only)

For most installations with cross-sections up to 50 mm², the cable reactance is negligibly small and a formula considering only resistance is sufficient.

Single-phase circuit (230 V):

ΔU%=2IBL100γSUn [%]\Delta U\% = \frac{2 \cdot I_B \cdot L \cdot 100}{\gamma \cdot S \cdot U_n} \ [\%]

Three-phase circuit (400 V):

ΔU%=3IBL100γSUn [%]\Delta U\% = \frac{\sqrt{3} \cdot I_B \cdot L \cdot 100}{\gamma \cdot S \cdot U_n} \ [\%]

where:
IBI_B — load current [A]
LL — cable length (one way) [m]
γ\gamma — material conductivity [m/(Ω·mm²)]
SS — cable cross-section [mm²]
UnU_n — nominal voltage [V]

Exact formula (with reactance)

For cross-sections of 70 mm² and above, the inductive reactance of the cable becomes significant, especially under inductive loads (motors). The full formula:

Single-phase circuit:

ΔU%=2IBL(rcosφ+xsinφ)100Un [%]\Delta U\% = \frac{2 \cdot I_B \cdot L \cdot (r \cdot \cos\varphi + x \cdot \sin\varphi) \cdot 100}{U_n} \ [\%]

Three-phase circuit:

ΔU%=3IBL(rcosφ+xsinφ)100Un [%]\Delta U\% = \frac{\sqrt{3} \cdot I_B \cdot L \cdot (r \cdot \cos\varphi + x \cdot \sin\varphi) \cdot 100}{U_n} \ [\%]

where:
rr — unit resistance of the cable [Ω/m]
xx — unit reactance of the cable [Ω/m] (typically 0.08 mΩ/m for cables)
cosφ\cos\varphi — load power factor

Conductivity of cable materials

Conductivity depends on the operating temperature of the cable. The values below account for the conductor operating temperature:

Materialγ at 20°Cγ at PVC (70°C)γ at XLPE (90°C)
Copper (Cu)56.044.442.4
Aluminium (Al)35.027.526.3

In voltage drop calculations, the conductivity corresponding to the cable operating temperature (70°C or 90°C) is used, not the ambient temperature. This gives a result on the "safe side" — the actual drop under lighter load will be lower.

Voltage drop tables — quick reference

The table below gives the voltage drop in %/(A·m) — simply multiply the value by the current and length to get the result in percent. Values for copper cables with PVC insulation (γ = 44.4):

Single-phase circuits 230 V
Cross-section [mm²]ΔU% per 1 A·mMax A·m at 3%Max A·m at 5%
1.50.01305230383
2.50.00783383639
40.004906121 020
60.003269201 534
100.001961 5312 551
160.001222 4594 098
250.000783 8466 410
350.000565 3578 929

How to use the table: Multiply the load current [A] by the route length [m]. If the result (A·m) is less than the value in the "Max A·m" column, the voltage drop is within the limit.

Example: A 6 A lighting circuit, 22 m long, 1.5 mm² cable. Product: 6 x 22 = 132 A·m. The limit for 3% is 230 A·m — within the limit (drop: 132 x 0.01305 = 1.72%).

Three-phase circuits 400 V
Cross-section [mm²]ΔU% per 1 A·mMax A·m at 5%
2.50.003901 282
40.002442 049
60.001633 067
100.0009755 128
160.0006108 197
250.00039012 821
350.00027917 921
500.00019525 641
Electrical distribution board with circuits

Cascading voltage drops

In a real installation, current flows through several cable sections: from the cable termination box, through the main supply line to the main distribution board, then to the floor distribution board, and from there to the load. The voltage drops on each section add up.

ΔU%total=ΔU%WLZ+ΔU%obwoˊd\Delta U\%_{total} = \Delta U\%_{WLZ} + \Delta U\%_{obwód}

The standard requires that the total voltage drop from the point of supply to the load does not exceed the permissible values (3% or 5%).

Cascading example

Installation in a multi-family building:

Section 1 — main supply line (three-phase 400 V):
Current: 63 A, length: 25 m, cross-section: 25 mm² Cu/PVC

ΔU%WLZ=3632510044,425400=272 650444 0000,61%\Delta U\%_{WLZ} = \frac{\sqrt{3} \cdot 63 \cdot 25 \cdot 100}{44{,}4 \cdot 25 \cdot 400} = \frac{272\ 650}{444\ 000} \approx 0{,}61\%

Section 2 — lighting circuit (single-phase 230 V):
Current: 8 A, length: 18 m, cross-section: 1.5 mm² Cu/PVC

ΔU%obwoˊd=281810044,41,5230=28 80015 3181,88%\Delta U\%_{obwód} = \frac{2 \cdot 8 \cdot 18 \cdot 100}{44{,}4 \cdot 1{,}5 \cdot 230} = \frac{28\ 800}{15\ 318} \approx 1{,}88\%

Total:

ΔU%total=0,61%+1,88%=2,49%\Delta U\%_{total} = 0{,}61\% + 1{,}88\% = 2{,}49\%

Permissible limit for lighting: 3%. The result of 2.49% — condition met, but with little margin. Increasing the lighting circuit length to 22 m would already give 3.10% — exceeding the standard.

DC cables of a photovoltaic installation on a roof

Voltage drop in photovoltaic installations (DC)

Photovoltaic installations are a special case — long cable runs on the direct current (DC) side from panels to the inverter, often outside the building. Every percent of voltage drop is a direct loss of installation power.

Formula for direct current (DC):

ΔU%=2IMPPL100γSUMPP [%]\Delta U\% = \frac{2 \cdot I_{MPP} \cdot L \cdot 100}{\gamma \cdot S \cdot U_{MPP}} \ [\%]

where:
IMPPI_{MPP} — current at maximum power point [A]
UMPPU_{MPP} — voltage at maximum power point [V]
LL — DC cable length (one way) [m]

The recommended voltage drop in PV installations is ≤ 1% on the DC side. Some standards allow 2%, but every additional percent is a real loss of annual energy production.

Example — 10 kWp PV installation

Data:
IMPPI_{MPP} = 11.5 A (2 strings of 5 panels, voltage approx. 200 V)
UMPPU_{MPP} = 200 V
LL = 25 m (panels on roof to inverter in garage)
Solar cable Cu 6 mm², γ = 56 (solar cable operates at a lower temperature than installation cable)

ΔU%=211,525100566200=57 50067 2000,86%\Delta U\% = \frac{2 \cdot 11{,}5 \cdot 25 \cdot 100}{56 \cdot 6 \cdot 200} = \frac{57\ 500}{67\ 200} \approx 0{,}86\%

The 0.86% drop is within the recommended 1%. For a longer run (e.g. 40 m), a 10 mm² cross-section should be considered.

Voltage drop during motor starting

Electric motors draw 5 to 8 times their rated current during starting. This momentary current surge causes a significant voltage drop, which can:

  • prevent motor starting (starting torque too low),
  • cause lighting to flicker throughout the installation,
  • disrupt the operation of other equipment on the circuit.
Example — heat pump motor

Data:
Compressor motor: InI_n = 16 A, starting current: IrozrI_{rozr} = 6 x 16 = 96 A
Supply: three-phase 400 V
Length: 30 m, cross-section: 6 mm² Cu/PVC

Voltage drop during operation:

ΔU%praca=3163010044,46400=83 138106 5600,78%\Delta U\%_{praca} = \frac{\sqrt{3} \cdot 16 \cdot 30 \cdot 100}{44{,}4 \cdot 6 \cdot 400} = \frac{83\ 138}{106\ 560} \approx 0{,}78\%

Voltage drop during starting:

ΔU%rozruch=3963010044,46400=498 831106 5604,68%\Delta U\%_{rozruch} = \frac{\sqrt{3} \cdot 96 \cdot 30 \cdot 100}{44{,}4 \cdot 6 \cdot 400} = \frac{498\ 831}{106\ 560} \approx 4{,}68\%

A 4.68% drop during starting means the voltage at the motor terminals will fall to approximately 381 V. For motors sensitive to voltage drop (e.g. scroll compressors), this can cause starting problems. Solutions:

  • increase the cross-section to 10 mm² (starting drop: 2.81%),
  • use a soft starter or variable frequency drive (VFD), which limits starting current,
  • shorten the cable run.

How to reduce voltage drop?

When the calculated voltage drop exceeds standards, there are several options:

1. Increase cable cross-section

The simplest solution — a thicker cable has lower resistance. Cost increases, but in many cases going up one cross-section size is sufficient.

2. Switch from single-phase to three-phase supply

Switching from 230 V to 400 V reduces the current by a factor of 3\sqrt{3} for the same power, and the three-phase formula yields a smaller drop:

Parameter1-ph 230 V3-ph 400 V
Power 10 kW, cos φ = 0.95I = 45.7 AI = 15.2 A
Cable 10 mm² Cu, L = 40 mΔU = 3.57%ΔU = 0.59%
Drop ratio6x smaller

Switching from single-phase to three-phase supply reduces the voltage drop by approximately 6 times for the same power and cross-section. This is particularly important for long cable runs to outbuildings or workshops.

3. Shorten the cable run

Voltage drop is directly proportional to length. Moving the distribution board closer to the load or routing the cable along a shorter path can solve the problem without changing the cross-section.

4. Split the load across more circuits

Instead of one circuit with high current — two circuits with lower current, each with a smaller voltage drop.

Long cable run to an outbuilding

When does voltage drop determine the cross-section?

In practice, voltage drop becomes more restrictive than current-carrying capacity in the following situations:

  • long cable runs (over 30-40 m) — outdoor lighting, garages, outbuildings, industrial halls,
  • lighting circuits — 3% limit instead of 5%,
  • aluminium cables — conductivity 38% lower than copper,
  • photovoltaic installations — recommended 1% limit on the DC side,
  • motor supply — need to account for starting current,
  • single-phase supply at high power — current is 3\sqrt{3} times higher than with three-phase supply.

In such cases, the voltage drop calculator will help you quickly determine whether the chosen cross-section is sufficient. If you need to select the entire circuit from scratch (including current-carrying capacity and correction factors), use the cable sizing calculator.

Summary

Voltage drop is a phenomenon that rarely poses a problem in short domestic circuits — but for longer cable runs, lighting, PV installations, or motor supply, it becomes a key design criterion. The most important rules:

  • Always check the voltage drop for cable runs over 30 m,
  • Sum the drops in cascade — main supply line + final circuit,
  • For PV installations, aim for a drop of ≤ 1% on the DC side,
  • For motors, account for starting current (5-8 x InI_n),
  • Three-phase supply reduces the drop by approx. 6x compared to single-phase,
  • Bonus: increasing the cross-section due to voltage drop typically also improves fault protection conditions (lower fault loop impedance = faster protective device tripping).

Use our voltage drop calculator to check the voltage drop for any circuit — just enter the power, voltage, length, and cable cross-section.

Back to articles list